AV-300i Version 2 User’s Guide
—————— Function Description ——————
Ch.1
65
At power up, the power converter firing and Ramp/speed regulation may be initiated if Terminal Enable and
Terminal Start/Stop are asserted (driven high).
Once Terminal Enable is asserted, no actuation occurrs until the Terminal Start/Stop is asserted. When this
occurs, the power converter firing is initiated, Motor magnetization sequence is executed, then Ramp and speed
regulation are unlocked.
When terminal Start/Stop is negated, the drive is stopped, and after the programmed delay power converter firing
is terminated.
Negating Terminal Enable will terminate converter firing at any time, and the motor will coast to a stop.
After a power fault, if Terminal enable and Terminal Start/Stop do not change, the drive will restart at power up.
Table 1.5.3.4-1: Example Setup for Unmanned Installation
Parameter description Index Value Comments
Command select 4002 "Terminal level"
En/Disable mode 4004 "Stop/FS & Spd=0"
Dig Enable src 0156 Do not care This source bypassed (AND logic)
Term StrStp src 0153 "DI 1 monitor" Tie Start/Stop signal to terminal 13
Dig StrStp src 0157 Do not care This source not used
Term Start src 9210 Do not care This source not used
Term Stop src 9211 Do not care This source not used
FStop src 0154 "NULL" Fast stop not used
Jog cmd src 8015
"NULL" Jog from the keyboard
Jog invers src 8018 "NULL" Jog inversion from the keyboard