AV-300i Version 2 User’s Guide
—————— Function Description ——————
Ch.1
29
NOTE! when the Regulation mode function is selected, the active regulation mode is displayed: in
order to enter the Select new mode press “Enter”.
1.3.2 Drive Starting Configurations (Startup Config)
With this menu configures:
- the Drive Setup
- the speed scale factor
- the Encoders
- the V/F control
- the motor and braking unit “I2t” protection
- and to use the recipes
1.3.2.1 Setup Mode (Enter setup mode)
Enter setup mode
It allows to enter the Setup mode where it is possible to set some Drive
parameters and the motor parameters, and to perform the data measur-
ing on the motor, autotune (with a moving or stopped rotor) for the
calculation of the current and flux loop gains.
Description:
STARTUP
Startup config
Enter setup mode
NOTE! the following description is valid when the SETUP MODE has been entered via Enter setup
mode. Every time it is required to enter and afterwards to exit the setup mode, the Drive
carries out the Restart procedure (the drive will take around 15 seconds). After saving the
setup, it is required to load the setup to have the drive usit.
SETUP MODE
Drive data Drive parameters
Mains voltage Power supply voltage (230 – 380 – 400 – 415 – 440 – 460)
Ambient temp Ambient temperature (40°C standard)
Switching freq PWM Switching frequency (2 – 4 – 8 – 16 kHz)
SPD ref/fbk res Resolution of the speed references (0 .125rpm, 0 . 250rpm, 0 . 500rpm)
Motor data Motor parameters
Rated voltage Motor rated voltage
Rated frequency Motor rated frequency
Rated current Motor rated current
Rated speed Motor rated speed
Rated power Motor rated power
Cosfi Motor cosΦ
Efficiency Motor efficiency
Load default mot It selects and loads the motor standard parameters:
Standard 400V or Standard 460V