GEH-6641E
—————— Function Description ——————
30
Ch.1
NOTE! by selecting one of the two factors, the motor standard parameters with 460V (or 400V) are
loaded making reference to the used Drive size. Through this process, old data is overwritten.
CurrentReg autotune Current loop self-tuning
Start ?
enabling of the data detection
Press
I
key
consent to the procedure start
Result Detected values (or Drive standard values):
Measured Rs resistance detected on the Stator
Measured Rr resistance detected on the Rotor
Measured Rr2 resistance2 detected on the Rotor
Measured DTL dead time limit
Measured DTS dead time slope
Measured LsSigma stator inductance
FluxReg autotune Flux loop self-tuning
Shaft rotating Self-tuning with a moving Rotor
Start ?
enabling of the data detection
Press
I
key
consent to the procedure start
Results detected values (or Drive standard values):
Measured P1 flux P1 coefficient of the flux curve
Measured P2 flux P2 coefficient of the flux curve
Measured P3 flux P3 coefficient of the flux curve
Measured ImNom value of the rated magnetizing current
Measured ImMax value of the maximum magnetizing current
Measures FluxNom value of the rated flux
Measures FluxMax value of the maximum flux
At standstill Self-tuning with a stopped Rotor
Start ?
enabling of the data detection
Press
I
key
consent to the procedure start
Results
Measured P1 flux P1 coefficient of the flux curve
Measured P2 flux P2 coefficient of the flux curve
Measured P3 flux P3 coefficient of the flux curve
Measured ImNom value of the rated magnetizing current
Measured ImMax value of the maximum magnetizing current
Measures FluxNom value of the rated flux
Measures FluxMax value of the maximum flux
Save setup Saving of the set and detected data
save as ? it allows to select 4 files where 4 different setups can be saved.
setup 0 selection of setup 0 – 1 – 2 – 3
Review setup Recall of the saved setup files
select setup ? it allows to select the saved setup file
setup 0 selection of setup 0 – 1 – 2 – 3
Exit setup mode Exit from the setup mode (the drive will take around 15 seconds)