"Stop/Fs&Spd=0". In this case the Start command must be recycled after Fast stop is no more
active in order to let the drive to start again.
Jog - this command provides momentary rotation of the drive with ramp and speed reference
settings independent of the ones defined for operation with Start/stop command.
NOTE! Start/Stop command takes priority over the Jog command. The Jog command can be
activated by concurrent sources: the [+/Jog] key on the keyboard, and a boolean source
that can be either a communication or application card or a programmable digital input. The
Jog command is complemented by a toggle command for rotation direction inversion. The
source of inversion may also be a dedicated key on the keyboard/display module or a
configurable source, both sources may be concurrently active.
NOTE! Due to the double function of the keys, it is initially necessary to hit [Shift] and [+/Jog] in
order to turn the keyboard section into jog mode. After that, the simple pressure of [+/Jog]
key will cause the drive to jog, and the pressure of the [-/<->] key will cause inversion of the
rotation. To exit keyboard jog mode press [</Escape].
1.5.2 Command Block (Commands)
The command Block, via the input sources, allows to select the signal origin to control:
- Term enable src command source for the terminal strip Enable
- Term StrStp src * source of the Start (1) command and of the terminal strip Stop (0) command
- Term Start src * command source for the terminal strip Start
- Term Stop src * command source for the terminal strip Stop
- Dig enable src digital Enable command source
- Dig StrStp src source of the Start (1) command and of the digital Stop (0) command.
- FastStop src Fast Stop command source
(*) The start and stop command can be controlled, as an alternative, via:
· A single terminal In this case (+24) 1 refers to the Start and (open) 0 to the Stop
+ 24V
START=Closed, STOP=open
· Two terminals connected with buttons In this case the change of state is caused by the positive
front (0 to1) on the terminal.
START
STOP
+ 24V
NOTE! For factory setup see section 1.5.3.1
NOTE! DI0, enable input, terminal point 12, has to be open to change parameter COMMANDS
SELECT from the keypad or toolbox.