5-76 D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP CHAPTER 5: SETTINGS
5
– "On" value defaults the input to logic 1
– "Off" value defaults the input to logic 0
– "Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
– "Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
RxGOOSE Boolean1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE Boolean1 FlexLogic operand are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
RxGOOSE DPS inputs
Navigate to Settings > Product Setup > Communications > IEC 618560 > GOOSE > RxGOOSE > RxGOOSE DPS Inputs.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the
user select the ones to add.
Figure 5-30: RxGOOSE DPS Inputs panel
RxGOOSE DPS1 ID
Range: 0 to 20 characters
Default: RxG DPS1
This setting allows the user to assign descriptive text to the names of the four RxGOOSE DPS1 FlexLogic operands. The
full operand name is the value of this setting appended with "Interm," "On," "Off," or "Bad." The standard and enhanced
front panels display the first 13 characters of this setting plus the state suffix to fit the 20 character display.
RxGOOSE DPS1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message containing the value that drives the RxGOOSE DPS1 FlexLogic operand. If set to
None, the RxGOOSE DPS1 FlexLogic operand assumes its default state.