EasyManuals Logo

GE D30 User Manual

GE D30
686 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #605 background imageLoading...
Page #605 background image
CHAPTER 9: THEORY OF OPERATION GROUND DIRECTIONAL OVERCURRENT
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 9-17
9
See the Application of Settings chapter for information on setting calculations.
9.3 Ground directional overcurrent
9.3.1 Description
Consider the negative-sequence directional overcurrent element. As shown, the negative-sequence voltage can be low
during internal fault conditions.
Figure 9-6: Offset impedance augmentation
In order to ensure operation of the element under such circumstances, the angle comparator uses a polarizing voltage
augmented by the negative-sequence current as per following equations:
Forward-looking element:
S_pol = -V_2 + I_2 x Z_offset x 1∠ECA
S_op = I_2 x 1∠ECA Eq. 9-8
Reverse-looking element:
S_pol = -V_2 + I_2 x Z_offset x 1∠ECA
S_op = -I_2 x 1∠ECA Eq. 9-9
Where ECA = forward ECA angle (maximum torque angle) and Z_offset = offset impedance. The effect of the augmentation
for forward and reverse fault is shown in the previous figure. As long as the offset impedance is not higher than the
negative-sequence line impedance, the element ensures correct and fast fault direction identification for both forward and
reverse faults. The same principle applies to the neutral directional overcurrent element.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D30 and is the answer not in the manual?

GE D30 Specifications

General IconGeneral
BrandGE
ModelD30
CategoryRelays
LanguageEnglish

Related product manuals