CHAPTER 5: SETTINGS PRODUCT SETUP
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-99
5
Figure 5-47: File transfer by IEC 61850
5.3.5.13 Web server HTTP protocol
SETTINGS PRODUCT SETUP  COMMUNICATIONS  WEB SERVER HTTP PROTOCOL
The D30 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the D30 “Main Menu.” Web pages are read-only and are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the
D30 and a computer to an Ethernet network, then enter the IP address of the D30 Ethernet port in a web browser.
To close the port, set the port number to 0.
Any change takes effect when the D30 is restarted.
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER(80): 80
Range: 0 to 65535 in steps of 1