EasyManuals Logo

GE D30 User Manual

GE D30
686 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #309 background imageLoading...
Page #309 background image
CHAPTER 5: SETTINGS PRODUCT SETUP
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-99
5
Figure 5-47: File transfer by IEC 61850
5.3.5.13 Web server HTTP protocol
SETTINGS PRODUCT SETUP  COMMUNICATIONS  WEB SERVER HTTP PROTOCOL
The D30 contains an embedded web server and can display pages in a web browser. The web pages are organized as a
series of menus that can be accessed starting at the D30 “Main Menu.” Web pages are read-only and are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the
D30 and a computer to an Ethernet network, then enter the IP address of the D30 Ethernet port in a web browser.
To close the port, set the port number to 0.
Any change takes effect when the D30 is restarted.
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER(80): 80
Range: 0 to 65535 in steps of 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D30 and is the answer not in the manual?

GE D30 Specifications

General IconGeneral
BrandGE
ModelD30
CategoryRelays
LanguageEnglish

Related product manuals