EasyManuals Logo

GE D30 User Manual

GE D30
686 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #338 background imageLoading...
Page #338 background image
5-128 D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP CHAPTER 5: SETTINGS
5
PUSHBTN 1 REMOTE — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the
PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
PUSHBTN 1 LOCAL — This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME — This setting applies only to “Self-Reset” mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by
PUSHBTN 1 SET remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL — This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the PUSHBUTTON 1 ON operand. This setting is not applied to
Pushbuttons 9 to 16 on the graphical front panel, where the label background shows the orange glow color for the "on"
state.
PUSHBTN 1 MESSAGE — This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the
PUSHBTN 1 ID and PUSHBTN 1 OFF TEXT settings. This settings has no effect on the
graphical front panel.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays when
the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the
FLASH MESSAGE TIME setting.
When set to "High Priority", the duration of the off message is as specified by the
FLASH MESSAGE TIME setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS — If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
The figures show the user-programmable pushbutton logic.