CHAPTER 5: SETTINGS FLEXLOGIC
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-169
5
FxE 2 to 8 Same set of operands as shown for FxE 1
ELEMENT:
Ground distance
GND DIST Z1 PKP
GND DIST Z1 OP
GND DIST Z1 OP A
GND DIST Z1 OP B
GND DIST Z1 OP C
GND DIST Z1 PKP A
GND DIST Z1 PKP B
GND DIST Z1 PKP C
GND DIST Z1 SUPN IA
GND DIST Z1 SUPN IB
GND DIST Z1 SUPN IC
GND DIST Z1 SUPN IN
GND DIST Z1 DPO A
GND DIST Z1 DPO B
GND DIST Z1 DPO C
GND DIST Z1 DIR SUPN
Ground distance zone 1 has picked up
Ground distance zone 1 has operated
Ground distance zone 1 phase A has operated
Ground distance zone 1 phase B has operated
Ground distance zone 1 phase C has operated
Ground distance zone 1 phase A has picked up
Ground distance zone 1 phase B has picked up
Ground distance zone 1 phase C has picked up
Ground distance zone 1 neutral 1A is supervising
Ground distance zone 1 neutral 1B is supervising
Ground distance zone 1 neutral 1C is supervising
Ground distance zone 1 neutral is supervising
Ground distance zone 1 phase A has dropped out
Ground distance zone 1 phase B has dropped out
Ground distance zone 1 phase C has dropped out
Ground distance zone 1 directional is supervising
GND DIST Z2 to 5 Same set of operands as shown for GND DIST Z1
ELEMENT:
Ground
instantaneous
overcurrent
GROUND IOC1 PKP
GROUND IOC1 OP
GROUND IOC1 DPO
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
GROUND IOC2 Same set of operands as shown for GROUND IOC 1
ELEMENT:
Ground time
overcurrent
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
GROUND TOC2 Same set of operands as shown for GROUND TOC1
ELEMENT:
Incipient cable fault
detection
INCIPNT FLT 1 OP
INCIPNT FLT 1 OP A
INCIPNT FLT 1 OP B
INCIPNT FLT 1 OP C
INCIPNT FLT 1 PKP
INCIPNT FLT 1 PKP A
INCIPNT FLT 1 PKP B
INCIPNT FLT 1 PKP C
Asserted when incipient cable fault detector 1 operates in any phase
Asserted when incipient cable fault detector 1 operates in phase A
Asserted when incipient cable fault detector 1 operates in phase B
Asserted when incipient cable fault detector 1 operates in phase C
Asserted when incipient cable fault detector 1 picks up in any phase
Asserted when incipient cable fault detector 1 picks up in phase A
Asserted when incipient cable fault detector 1 picks up in phase B
Asserted when incipient cable fault detector 1 picks up in phase C
ELEMENT:
Non-volatile latches
LATCH 1 ON
LATCH 1 OFF
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16 Same set of operands as shown for LATCH 1
ELEMENT:
Line pickup
LINE PICKUP OP
LINE PICKUP PKP
LINE PICKUP DPO
LINE PICKUP I<A
LINE PICKUP I<B
LINE PICKUP I<C
LINE PICKUP UV PKP
LINE PICKUP LEO PKP
LINE PICKUP RCL TRIP
Line pickup has operated
Line pickup has picked up
Line pickup has dropped out
Line pickup detected phase A current below 5% of nominal
Line pickup detected phase B current below 5% of nominal
Line pickup detected phase C current below 5% of nominal
Line pickup undervoltage has picked up
Line pickup line end open has picked up
Line pickup operated from overreaching zone 2 when reclosing the line (zone
1 extension functionality)
ELEMENT:
Load encroachment
LOAD ENCHR PKP
LOAD ENCHR OP
LOAD ENCHR DPO
Load encroachment has picked up
Load encroachment has operated
Load encroachment has dropped out
ELEMENT:
Negative-sequence
directional
overcurrent
NEG SEQ DIR OC1 FWD
NEG SEQ DIR OC1 REV
NEG SEQ DIR OC2 FWD
NEG SEQ DIR OC2 REV
Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence directional overcurrent 1 reverse has operated
Negative-sequence directional overcurrent 2 forward has operated
Negative-sequence directional overcurrent 2 reverse has operated
ELEMENT:
Negative-sequence
instantaneous
overcurrent
NEG SEQ IOC1 PKP
NEG SEQ IOC1 OP
NEG SEQ IOC1 DPO
Negative-sequence instantaneous overcurrent 1 has picked up
Negative-sequence instantaneous overcurrent 1 has operated
Negative-sequence instantaneous overcurrent 1 has dropped out
NEG SEQ IOC2 Same set of operands as shown for NEG SEQ IOC1
Operand type Operand syntax Operand description

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D30 and is the answer not in the manual?

GE D30 Specifications

General IconGeneral
BrandGE
ModelD30
CategoryRelays
LanguageEnglish

Related product manuals