Size 0 and 1 (Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
TEC &
TECL
Rating
Mag-Break
Trip Setting
Rec. Max.
66-.76 C087A 3 LO LO
.77-.84 C097A 3 LO LO
.85-.93 C109A 3 LO 1
.94-1.04 C118A 3 LO 1
1.05-1.15 C131A 3 LO 2
1.16-1.27 C148A 3 LO 2
1.28-1.39 C163A 3 LO 3
1.40-1.55 C184A 3 LO 4
1.56-1.73 C196A 3 1 4
1.74-1.89 C220A 3 1 5
1.90-2.05 C239A 3 2 6
2.06-2.28 C268A 3 2 7
2.29-2.47 C301A 3 3 8
2.29-2.47 C301A 7 LO 1
2.48-2.79 C326A 7 LO 2
2.80-3.31 C356A 7 LO 3
3.32-3.70 C379A 7 LO 4
3.71-4.06 C419A 7 1 5
4.07-4.47 C466A 7 1 5
4.48-4.95 C526A 7 2 6
4.96-5.49 C592A 7 2 7
4.96-5.49 C592A 15 LO 1
5.50-5.91 C630A 7 3 8
5.50-5.91 C630A 15 LO 2
5.92-6.47 C695A 15 LO 2
6.48-7.20 C778A 15 LO 3
7.21-8.22 C867A 15 LO 3
8.23-8.72 C955A 15 1 4
8.73-9.67 C104B 15 1 5
9.68-10.4 C113B 15 1 6
10.5-11.0 C125B 15 2 7
11.1-12.4 C137B 15 2 7
11.1-12.4 C137B 30 LO 2
12.5-13.2 C151B 30 LO 2
13.3-15.4 C163B 30 LO 3
15.5-17.1 C180B 30 LO 4
Size 1
17.2-18.1 C198B 30 1 5
18.2-20.0 C214B 30 1 5
20.1-21.5 C228B 30 2 6
21.6-22.5 C250B 30 2 7
22.6-23.9 C273B 30 2 8
22.6-23.9 C273B 50 LO 2
24.0-26.0 C303B 30 3 8
24.0-26.0 C303B 50 LO 3
26
.1-27.0 C330B 50 LO 4
Size 2 (Standard)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
TEC &
TECL
Rating
Mag-Break
Trip Setting
Rec. Max.
8.81-9.27 C104B 15 2 5
9.28-9.99 C113B 15 2 6
10.0-11.1 C125B 15 3 6
11.2-12.1 C137B 15 3 7
11.2-12.1 C137B 30 LO 2
12.2-13.0 C151B 15 4 8
12.2-13.0 C151B 30 LO 2
13.1-15.5 C163B 30 1 3
15.6-16.8 C180B 30 1 4
16.9-18.0 C198B 30 2 5
18.1-19.7 C214B 30 2 5
19.8-21.6 C228B 30 2 6
21.7-23.9 C250B 30 3 7
21.7-23.9 C250B 50 LO 2
24.0-25.5 C273B 30 3 8
24.0-25.5 C273B 50 LO 3
25.6-26.0 C303B 30 3 9
25.6-28.2 C303B 50 LO 3
28.3-31.6 C330B 50 1 4
31.7-34.7 C366B 50 2 5
34.8-37.8 C400B 50 2 6
37.9-40.6 C440B 50 3 7
40.7-43.4 C460B 50 3 8
Size 2 (Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
TEC &
TECL
Rating
Mag-Break
Trip Setting
Rec. Max.
9.04-9.61 C104B 15 2 5
9.62-10.5 C113B 15 2 6
10.6-11.6 C125B 15 3 7
11.7-12.5 C137B 15 3 8
11.7-12.5 C137B 30 LO 2
12.6-13.0 C151B 15 4 9
12.6-13.6 C151B 30 LO 3
13.7-16.7 C163B 30 1 3
16.8-17.9 C180B 30 1 5
18.0-18.7 C198B 30 2 5
18.8-20.4 C214B 30 2 6
20.5-22.7 C228B 30 2 7
22.8-24.7 C250B 30 3 8
22.8-24.7 C250B 50 LO 2
24.8-26.0 C273B 30 4 9
24.8-26.3 C273B 50 LO 4
26.4-29.5 C303B 50 LO 4
29.6-32.5 C330B 50 1 4
32.6-36.7 C366B 50 2 6
36.8-41.9 C400B 50 2 7
42.0-43.2 C440B 50 3 9
43.3-43.4 C460B 50 3 9
Size 3 (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
TEC &
TECL
Rating
Mag-Break
Trip Setting
Rec. Max.
17.8-18.4 F233B 30 1 5
18.5-21.1 F243B 30 1 6
21.2-22.1 F270B 30 2 7
22.2-26.0 F300B 30 3 7
26.1-28.0 F327B 50 LO 4
28.1-31.3 F357B 50 LO 4
31.4-33.3 F395B 50 1 5
33.4-34.3 F430B 50 1 6
34.4-40.9 F487B 50 1 6
41.0-43.4 F567B 50 2 8
43.5-44.7 F567B 100 LO 3
44.8-51.0 F614B 100 LO 3
51.1-52.0 F658B 100 1 4
52.1-55.4 F719B 100 1 4