Evolution Series E9000 User Manual
37
37
Size 3 (Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
17.8-18.4 F233B 70
18.5-21.1 F243B 80
21.2-22.1 F270B 80
22.2-26.1 F300B 90
26.2-28.0 F327B 100
28.1-31.3 F357B 110
1
31.4-33.3 F395B 125
1
33.4-34.3 F430B 125
1
34.4-40.9 F487B 150
1
41.0-44.7 F567B 150
1
44.8-51.0 F614B 175
1
51.1-52.0 F658B 200
1
52.1-55.4 F719B 200
1
55.5-63.3 F772B 200
1
63.4-66.1 F848B 200
1
66.2-73.5 F914B 200
1
73.6-82.2 F104C 200
1
82.3-90.0 F114C 200
1
Size 1 (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
27.1-32.2 F357B 110
32.3-34.0 F395B 125
34.1-36.8 F430B 125
36.9-44.6 F487B 150
44.7-48.4 F567B 175
48.5-53.9 F614B 175
54.0-57.4 F658B 200
57.5-60.0 F719B 225
1
60.1-69.5 F772B 225
1
69.6-71.7 F848B 250
1
71.8-79.9 F914B 275
1
80.0-92.3 F104C 300
1
92.4-97.0 F114C 350
1
97.1-108 F118C 400
1
109-118 F133C 400
1
119-131 F149C 400
1
132-135 F161C 400
1
Size 3 (Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
28.8-32.0 F357B 110
32.1-34.2 F395B 125
34.3-36.7 F430B 125
36.8-43.9 F487B 150
44.0-46.6 F567B 175
46.7-52.6 F614B 175
52.7-55.6 F658B 200
55.7-58.7 F719B 225
1
58.8-67.1 F772B 225
1
67.2-70.6 F848B 250
1
70.7-76.3 F914B 275
1
76.4-88.7 F104C 300
1
88.8-93.4 F114C 350
1
93.5-105 F118C 350
1
106-114 F133C 400
1
115-128 F149C 400
1
129-131 F161C 400
1
132-135 F174C 400
1
Size 5 – 300:15CT (Standard and Ambient Comp.)
Motor Full-
Load Amps
3-Ph, 3 Heater
Heater
Number
CR123
Maximum
Fuse
Rating
109-118 C592A 600
119-128 C630A 600
129-138 C695A 600
139-155 C778A 600
156-168 C867A 600
169-184 C955A 600
185-200 C104B 600
201-221 C113B 600
222-237 C125B 600
238-262 C137B 600
263-270 C151B 600
Electronic Overload Table for Fusible Controllers
Tripping current is 120% of Dial setting. Motors with 1.15-1.25 service
factor, set dial to motor FLA Motors with 1.0 service factor, set dial to
0.9 motor FLA.
NEMA Size FLA Range in Amps Catalog Number Max. Fuse in Amps
1 0.8 to 1.59 CR324CXD Class R 30 Class J 60
1 1.6 to 3.19 CR324CXE
1 3.2 to 6.49 CR324CXF
1 6.5 to 12.8 CR324CXG
1 13 to 27 CR324CXH
2 13 to 25.6 CR324DXG 60 100
2 26 to 49.9 CR324DXH
2 50 to 100 CR324DXJ
3 17 to 34.9 CR324FXK 100 200
3 35 to 64.9 CR324FXL
3 65 to 90 CR324FXM
4 17 to 34.9 CR324FXK 200 400
4 35 to 64.9 CR324FXL
4 65 to 135 CR324FXM
5
1
32 to 64.0 CR324GXN 400 600
5
1
65 to 129.9 CR324GXP
5
1
130 to 270 CR324GXQ
6
2
130 to 259.9 CR324HXS 600 Class L 1200
6
2
260 to 540 CR324HXT
1
300:15 CT’s
2
800:5 CT’s
Additional motor overload protection required
for MM200 abd MM300 relay applications with
FLA less than 6A.
1
See maximum fuse and short-circuit rating table on page 29