350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5–1
350 Feeder Protection System
Chapter 5: Quick setup - Front
control panel
Digital Energy
Multilin
Quick setup - Front control panel
The “Quick Setup” utility is part of the 350 relay main menu, and can be used for quick and
easy programming. Power system parameters, and settings for some simple over-current
elements can be easily set. Use the “Quick Setup” utility to program the following:
Power System Data:
•Phase CT Primary
Ground CT Primary
VT Secondary voltage
Aux VT Secondary Voltage
•Aux VT Ratio
Overcurrent Protection:
•Phase TOC
Ground TOC
•Neutral TOC
•Phase IOC
Ground IOC
•Neutral IOC
NOTE
NOTE:
Ensure the relay is in "Relay Ready" state before using Quick Setup.