EasyManuals Logo

GE Multilin 350 Series User Manual

GE Multilin 350 Series
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #183 background imageLoading...
Page #183 background image
CHAPTER 6: SETPOINTS S3 PROTECTION
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–67
Figure 17: Phase instantaneous overcurrent protection logic diagram
SETPOINT
Phase A current (IA)
RUN
SETPOINT
PH IOC FUNCTION:
Disabled = 0
Latched Alarm
PH IOC PICKUP:
PH IOC PKP DELAY:
AND
Phase B current (IB)
Phase C current (IC)
RUN
RUN
Operate Output Relay 1 (TRIP)
Event Recorder
Transient Recorder
LED: PICKUP
LED: TRIP
Event Recorder
Transient Recorder
Alarm
OR
OR
Cold Load PKP
Autoreclose
(per shot settings)
Phase Currents
Block Inputs
AND
SETPOINT:
Operate
output relays
upon
selection
OUTPUT RELAY 4
OUTPUT RELAY 5
OUTPUT RELAY 6
OUTPUT RELAY 3
Trip
AND
SETPOINT
BLOCK 1:
Off=0
BLOCK 2:
Off=0
BLOCK 3:
Off=0
OR
Message
Phase IOC OP
IB >
PICKUP
IA > PICKUP
IC >
PICKUP
SETPOINT
Phase IOC AOP
Phase IOC
BOP
Phase IOC COP
Phase IOC A PKP
Phase IOC B PKP
Phase IOC C PKP
Phase IOC PKP
Message
t
PKP
0
t
PKP
0
t
PKP
0
OR
OR
Trip
(To Breaker Failure)
LED: ALARM
RESET
Command
AND
S
R
LATCH
898009.cdr
Courtesy of NationalSwitchgear.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin 350 Series and is the answer not in the manual?

GE Multilin 350 Series Specifications

General IconGeneral
BrandGE
ModelMultilin 350 Series
CategoryRelays
LanguageEnglish

Related product manuals