CHAPTER 6: SETPOINTS S3 PROTECTION
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–93
Figure 29: Phase undervoltage logic diagram
Phase Voltage Inputs
(associated setpoints)
SETPOINTS
Vab
SETPOINT
PH UV FUNCTION:
Disabled = 0
Latched Alarm
PH UV PICKUP:
PH UV CURVE:
PH UV DELAY:
AND
Vbc
Vca
Operate Output Relay 1 (TRIP)
Event Recorder
LED: TRIP
Alarm
OR
OR
AND
SETPOINTS
Operate
output relays
upon
selection
OUTPUT RELAY 4
OUTPUT RELAY 5
OUTPUT RELAY 6
OUTPUT RELAY 3
Trip
AND
Trip
(To Breaker Failure)
SETPOINTS
BLOCK 1:
Off=0
BLOCK 2:
Off=0
BLOCK 3:
Off=0
OR
RUN
RUN
RUN
PICKUP
Van
Vbn
Vcn
None
PICKUP
PICKUP
Van or Vab > Minimum
Vbn or Vbc > Minimum
Vcn or Vca > Minimum
PH UV MIN VOLTAGE:
SETPOINT
AND
AND
AND
Delta
Wye
All Three
Any One
Any Two
Operate for
programmed
combination
Any Two
Any One
All Three
Pickup for
Programmed
Combination
SETPOINT
PH UV PHASES:
OR
OR
LED: PICKUP
Phase Undervoltage
Message
LED: ALARM
RESET
Command
AND
S
R
LATCH
898014A1.cdr