6–104 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
Figure 35: Auxiliary Overvoltage logic diagram
Auxiliary Voltage Input
(associated setpoints)
SETPOINTS
SETPOINT
AUX OV FUNCTION:
Disabled = 0
Latched Alarm
AUX OV PICKUP:
AND
Operate Output Relay 1 (TRIP)
Event Recorder
LED: TRIP
Alarm
OR
OR
AND
SETPOINTS
Operate
output relays
upon
selection
OUTPUT RELAY 4
OUTPUT RELAY 5
OUTPUT RELAY 6
OUTPUT RELAY 3
Trip
AND
Trip
(To Breaker Failure)
SETPOINTS
BLOCK 1:
Off=0
BLOCK 2:
Off=0
BLOCK 3:
Off=0
OR
RUN
Aux V
LED: PICKUP
Aux. OV Trip (Alarm) - PKP, OP, DPO
Message
V > PICKUP
AUX OV DELAY:
SETPOINT
t
PKP
LED: ALARM
RESET
Command
AND
S
R
LATCH
898011A1.cdr
Courtesy of NationalSwitchgear.com