CHAPTER 6: SETPOINTS S4 CONTROLS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–121
Figure 42: Logic Element logic diagram
SETPOINT
TRIGGER SOURCE 1
Off
TRIGGER SOURCE 2
Off
TRIGGER SOURCE 3
Off
SETPOINT
BLOCK 1
Off
BLOCK 2
Off
BLOCK 3
Off
AND
PKP TIME DELAY
SETPOINT
t
PKP
t
RST
LE1 ASSERTED STATE:
SETPOINT
t
PKP
Off
On
Event Recorder
Transient Recorder
SETPOINT
OUTPUT RELAY 4
OUTPUT RELAY 5
OUTPUT RELAY 6
OUTPUT RELAY 3
RST TIME DELAY
Logic Elem1 OP
Logic Elem1 PKP
LED: PICKUP
Message
SETPOINT
LOGIC EL FUNCTION
Disabled = 0
Latched Alarm
Operate Output Relay 1 (TRIP)
LED: ALARM
LED: TRIP
Alarm
OR
OR
AND
RESET
Command
Trip
AND
AND
Control
S
R
LATCH
898755A1.cdr
Logic Elem1 DPO
t
PKP
TRIGGER LOGIC
SETPOINT
AND
OR
t
PKP
BLOCK LOGIC
SETPOINT
AND
OR
Operate
output relays
upon
selection