GEK-113285A G650 Generator Protection & Control System B-133
APPENDIX B B.7 MEMORY MAP
B
0x4412 PF Stg2 Trip Delay F003 1 R/W 2 [0.2 , 300.0] s
0x4414 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x441E Confirmation address W 1
Ajustes Limitador Factor de Potencia Grupo 3 - Pwr Factor Limiting 3 Settings(Enhanced models only)
0x441F Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4420 PF Lead Stg1 Level F003 1 R/W 2 [0.05 , 0.99]
0x4422 PF Lag Stg1 Level F003 1 R/W 2 [0.05 , 0.99]
0x4424 PF Stg1 Trip Delay F003 1 R/W 2 [0.2 , 300.0] s
0x4426 PF Lead Stg2 Level F003 1 R/W 2 [0.05 , 0.99]
0x4428 PF Lag Stg2 Level F003 1 R/W 2 [0.05 , 0.99]
0x442A PF Stg2 Trip Delay F003 1 R/W 2 [0.2 , 300.0] s
0x442C Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4436 Confirmation address W 1
Ajustes Energización Accidental Grupo 1 - Accidental Energization 1 Settings
0x4437 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4438 Accdnt Enrg Mode F012 1 R/W 1 0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x4439 Overcurrent pickup F003 1 R/W 2 [0.00 , 160.00] A
0x443B Ph Undervoltage pickup F003 1 R/W 2 [0.00 , 500.00] V
0x443D Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4447 Confirmation address W 1
Ajustes Energización Accidental Grupo 2 - Accidental Energization 2 Settings
0x4448 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4449 Accdnt Enrg Mode F012 1 R/W 1 0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x444A Overcurrent pickup F003 1 R/W 2 [0.00 , 160.00] A
0x444C Ph Undervoltage pickup F003 1 R/W 2 [0.00 , 500.00] V
0x444E Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4458 Confirmation address W 1
Ajustes Energización Accidental Grupo 3 - Accidental Energization 3 Settings
0x4459 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x445A Accdnt Enrg Mode F012 1 R/W 1 0=UV AND OFF-LINE
1=UV OR OFF-LINE
0x445B Overcurrent pickup F003 1 R/W 2 [0.00 , 160.00] A
0x445D Ph Undervoltage pickup F003 1 R/W 2 [0.00 , 500.00] V
0x445F Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x4469 Confirmation address W 1
Ajustes Sobretensión Tierra Grupo 1 - Ground OV 1 Settings
0x446A Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x446B Pickup Level F003 1 R/W 2 [3 , 500] V
0x446D Trip Delay F003 1 R/W 2 [0.00 , 900.00] s
0x446F Reset Delay F003 1 R/W 2 [0.00 , 900.00] s
0x4471 Snapshot Events F012 1 R/W 1 0=DISABLED
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS