B-134 G650 Generator Protection & Control System GEK-113285A
B.7 MEMORY MAP APPENDIX B
1=ENABLED
0x447B Confirmation address W 1
Ajustes Sobretensión Tierra Grupo 2 - Ground OV 2 Settings
0x447C Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x447D Pickup Level F003 1 R/W 2 [3 , 500] V
0x447F Trip Delay F003 1 R/W 2 [0.00 , 900.00] s
0x4481 Reset Delay F003 1 R/W 2 [0.00 , 900.00] s
0x4483 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x448D Confirmation address W 1
Ajustes Sobretensión Tierra Grupo 3 - Ground OV 3 Settings
0x448E Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x448F Pickup Level F003 1 R/W 2 [3 , 500] V
0x4491 Trip Delay F003 1 R/W 2 [0.00 , 900.00] s
0x4493 Reset Delay F003 1 R/W 2 [0.00 , 900.00] s
0x4495 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x449F Confirmation address W 1
Datos Ecuaciones PLC - PLC Data
0x6000 PLC equations F009 R 15360
Datos Display Gráfico - LCD Data
0x9C00 LCD configuration R 768
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS