F-16 G650 Generator Protection & Control System GEK-113285A
F.1 FACTORY DEFAULT SETTINGS APPENDIX F
F
SETPOINT > CONTROL ELEMENTS > BREAKER FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Supervision (retrip) pickup level Supervision Pickup 1.00 0.01 A [0.05 : 160.00]
Hiset pickup level Hiset Pickup 5.00 0.01 A [0.05 : 160.00]
Lowset pickup level Lowset Pickup 2.00 0.01 A [0.05 : 160.00]
Internal arc pickup level Internal Arc Pickup 0.10 0.01 A [0.05 : 160.00]
Internal arc time delay Internal Arc Delay 10.00 0.01 s [0.00 : 900.00]
Retrip time delay Supervision Delay 10.00 0.01 s [0.00 : 900.00]
Hiset time delay HiSet Delay 10.00 0.01 s [0.00 : 900.00]
Lowset time delay LowSet Delay 10.00 0.01 s [0.00 : 900.00]
Second stage time delay 2nd Step Delay 10.00 0.01 s [0.00 : 900.00]
WITHOUT current element time delay No Current Delay 10.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE(ENHANCED MODELS ONLY)
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function
DISABLED
N/A [DISABLED – ENABLED]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1 > FREQUENCY RATE OF CHANGE 2 > FREQUENCY RATE OF CHANGE 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function Permission Function DISABLED N/A [DISABLED – ENABLED]
Direction of the frequency change Freq. Rate Trend INCREASING N/A
[INCREASING -
DECREASING - BI-
DIRECTIONAL]
Operation Value in Hz/s Freq. Rate Pickup 0.50 0.01 Hz/s [0.10 : 10.00]
Minimum required voltage in %
nominal voltage
Freq. Rate OV Supv 40.00 0.01% [0.00 : 110.00]
Minimum Frequency Threshold Freq. Rate Min 45.00 0.01 Hz [20.00 : 80.00]
Maximum Frequency Threshold Freq. Rate Max 65.00 0.01 Hz [20.00 : 80.00]
Frequency rate Trip Delay Freq. Rate Delay 0.00 0.01 s [0.00 : 60.00]
Snapshot Events Generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > LOSS OF MAINS(ENHANCED MODELS ONLY
LOSS OF MAINS 1 > LOSS OF MAINS 2 > LOSS OF MAINS 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function Permission Function DISABLED N/A [DISABLED – ENABLED]
Any phase or three phase
displacement mode to operate
Loss of Mains Mode ONE PHASE N/A [ONE PHASE ]
Minimum Phase shift angle value to
operate
Phase Shift Angle 1.00 0.01 Deg [2.00 : 22.00]
Minimum voltage threshold Minimum Voltage 70 1 V [30 : 500]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > LOSS OF EXCITATION