GEK-113285A G650 Generator Protection & Control System F-17
APPENDIX F F.1 FACTORY DEFAULT SETTINGS
F
LOSS OF EXCITATION 1 > LOSS OF EXCITATION 2 > LOSS OF EXCITATION 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function Permission Function DISABLED N/A [DISABLED – ENABLED]
Center point in Ohms (sec) for Stage 1 Stage 1 Center 10.00 0.01 Ohm [0.10 : 300.00]
Radius value in Ohms (sec) for Stage
1
Stage 1 Radius 8.00 0.01 Ohm [0.10 : 300.00]
UV Supervision for stage 1 Stage 1 UV Supv DISABLED N/A [DISABLED – ENABLED]
Trip time for Stage 1 Stage 1 Trip Delay 0.05 0.01 s [0.00 : 65.54]
Center point in Ohms (sec) for Stage 2 Stage 2 Center 10.00 0.01 Ohm [0.10 : 300.00]
Radius value in Ohms (sec) for Stage
2
Stage 2 Radius 8.00 0.01 Ohm [0.10 : 300.00]
UV Supervision for stage 2 Stage 2 UV Supv DISABLED N/A [DISABLED – ENABLED]
Trip time for Stage 2 Stage 2 Trip Delay 0.05 0.01 s [0.00 : 65.54]
UV Supervision Level for both stages
1 and 2
UV Supv Level 40.0 0.1 V [0.0 : 500.0]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]