F-18 G650 Generator Protection & Control System GEK-113285A
F.1 FACTORY DEFAULT SETTINGS APPENDIX F
F
SETPOINT > CONTROL ELEMENTS > ACCIDENTAL ENERGIZATION
ACCIDENTAL ENERGIZATION 1 > ACCIDENTAL ENERGIZATION 2 > ACCIDENTAL ENERGIZATION 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function Permission Function DISABLED N/A [DISABLED – ENABLED]
Arming mode for Accidental
Energization
Accdnt Enrg Mode UV AND OFF-LINE N/A [UV AND OFF-LINE – UV
OR OFF-LINE]
Overcurrent Level to operate Overcurrent pickup 1.50 0.01 A [0.00 : 160.00]
Arming undervoltage value Ph Undervoltage
pickup
40.00 0.01 V [0.00 : 500.00]
Snapshot Event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]