F-22 G650 Generator Protection & Control System GEK-113285A
F.2 FACTORY DEFAULT CONFIGURATION APPENDIX F
F
CONT OP RESET_G_07 Not Configured
CONT OP RESET_G_08 Not Configured
SETPOINT>RELAY CONFIGURATION>LEDS
LED ID LED NAME SOURCE SIGNAL LOGIC SOURCE
LOGIC
LED01 TRIP VO_083_GENERAL_TRIP
LED02 50/51P TRIP VO_019_PHASE_OVERCURRENT_TRIP
LED03 50/51G TRIP VO_069_GROUND_OVERCURRENT_TRIP
LED04 50_2/51_2 TRIP VO_061_51-2_TRIP
VO_041_50-1_TRIP
LED05 27 TRIP VO_073_27P_TRIP
LED06 59 TRIP VO_100_LED_59P_TRIP
LED07 81TRIP VO_101_LED_81_TRIP
LED08 PICKUP VO_085_GENERAL_PKP
LED09 50/51P PICKUP VO_007_PHASE_OVERCURRENT_PKP
LED10 50/51G PICKUP VO_009_GROUND_OVERCURRENT_PKP
LED11 50_2/51_2 PKP VO_006_51-2_PKP
VO_033_50-2_PKP
LED12 27 PICKUP VO_045_27P_PKP
LED13 59 PICKUP VO_046_59P_PKP
LED14 81U/O PICKUP VO_054_81O_PKP
VO_055_81U_PKP
LED15 81R PICKUP VO_052_81DF-DT PKP
SETPOINT>RELAY CONFIGURATION>PROTECTION ELEMENTS
PROTECTION ELEMENT SOURCE SIGNAL LOGIC SOURCE LOGIC
LED RESET INPUT OPERATION BIT 3
CHANGE LOCAL-
REMOTE
Not Configured
CHANGE OP BLOCKED Not Configured
HMI BACKLIGHT ON Not Configured
HMI BACKLIGHT OFF Not Configured
PH IOC1 HIGH A BLK GROUP 1 BLOCKED
LVI_1_BLOCK 50PH
PH IOC1 HIGH B BLK GROUP 1 BLOCKED
LVI_1_BLOCK 50PH
PH IOC1 HIGH C BLK GROUP 1 BLOCKED
LVI_1_BLOCK 50PH
PH IOC2 HIGH A BLK GROUP 2 BLOCKED
LVI_1_BLOCK 50PH
PH IOC2 HIGH B BLK GROUP 2 BLOCKED
LVI_1_BLOCK 50PH
PH IOC2 HIGH C BLK GROUP 2 BLOCKED
LVI_1_BLOCK 50PH
PH IOC3 HIGH A BLK GROUP 3 BLOCKED
LVI_1_BLOCK 50PH
PH IOC3 HIGH B BLK GROUP 3 BLOCKED
LVI_1_BLOCK 50PH
PH IOC3 HIGH C BLK GROUP 3 BLOCKED
LVI_1_BLOCK 50PH
NEUTRAL IOC1 BLOCK GROUP 1 BLOCKED
NEUTRAL DIR1 OP NOT
SETPOINT>RELAY CONFIGURATION>OUTPUTS
OUTPUT ID OUTPUT NAME SOURCE SIGNAL LOGIC SOURCE LOGIC