GE Multilin N60 Network Stability and Synchrophasor Measurement System 4-29
4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE
4
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic operand is set to “On” and the
N60 does not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
REMOTE ACCESS DENIED FlexLogic operand is set to “Off” after the expiration of the ten-minute timeout.