6-10 N60 Network Stability and Synchrophasor Measurement System GE Multilin
6.2 STATUS 6 ACTUAL VALUES
6
6.2.16 IEC 61850 GOOSE INTEGERS
PATH: ACTUAL VALUES  STATUS  IEC 61850 GOOSE UINTEGERS
The N60 Network Stability and Synchrophasor Measurement System is provided with optional IEC 61850
communications capability. This feature is specified as a software option at the time of ordering. See the
Order Codes section in chapter 2 for details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
6.2.17 DIRECT INTEGER INPUTS
PATH: ACTUAL VALUES  STATUS  DIRECT INTEGER INPUTS
The direct integer input data points display in this menu. They are received via direct input and output messages sent from
other devices.
6.2.18 TELEPROTECTION CHANNEL TESTS
PATH: ACTUAL VALUES STATUS  TELEPROT CH TESTS
The status information for two channels is shown here.
IEC 61850
GOOSE UINTEGERS
UINT INPUT 1
0
MESSAGE
UINT INPUT 2
0
MESSAGE
UINT INPUT 16
0
DIRECT INTEGER
INPUTS
UINT INPUT 1
0
MESSAGE
UINT INPUT 2
0
MESSAGE
UINT INPUT 16
0
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 1 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
MESSAGE
CHANNEL 2
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 2 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
MESSAGE
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
Range: n/a, FAIL, OK