GE Multilin N60 Network Stability and Synchrophasor Measurement System 5-155
5 SETTINGS 5.5 FLEXLOGIC
5
Figure 5–53: FLEXELEMENT DIRECTION, PICKUP, AND HYSTERESIS
In conjunction with the
FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac-
teristics as shown in the figure below.
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
PICKUP
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
PICKUP
HYSTERESIS = % of PICKUP
842705A1.CDR