GE Multilin N60 Network Stability and Synchrophasor Measurement System 7-3
7 COMMANDS AND TARGETS 7.1 COMMANDS
7
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
7.1.4 SET DATE AND TIME
PATH: COMMANDS  SET DATE AND TIME
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time is
over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
7.1.5 RELAY MAINTENANCE
PATH: COMMANDS  RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The
PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE
ORDER CODE
command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the
ORDER
CODE NOT UPDATED
message will be shown.
The
REBOOT RELAY COMMAND reboots the relay so that changes to configuration settings can take effect. In most cases, if
changes are made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator or Operator role can initiate the Reboot Relay command.
The SERVICE COMMAND is used to perform specific N60 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the N60 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the N60 is shipped from the factory,
 COMMANDS
 SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
(YYYY/MM/DD HH:MM:SS)
 COMMANDS
 RELAY MAINTENANCE
PERFORM LAMPTEST?
No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
REBOOT RELAY?
No
Range: No, Yes
SERVICE COMMAND:
0
Range: 0, 101
SAVE VOLATILE DATA?
No
Range: No, Yes
UPDATING...
PLEASE WAIT