B-14 N60 Network Stability and Synchrophasor Measurement System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
07EC ...Repeated for IEC103 Command 28
07F0 ...Repeated for IEC103 Command 29
07F4 ...Repeated for IEC103 Command 30
07F8 ...Repeated for IEC103 Command 31
07FC ...Repeated for IEC103 Command 32
Digital Counter States (Read Only Non-Volatile) (8 Modules)
0800 Digital Counter 1 Value -2147483647 to
2147483647
--- 1 F004 0
0802 Digital Counter 1 Frozen -2147483647 to
2147483647
--- 1 F004 0
0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 --- 1 F050 0
0806 Digital Counter 1 Frozen Time Stamp us 0 to 4294967295 --- 1 F003 0
0808 ...Repeated for Digital Counter 2
0810 ...Repeated for Digital Counter 3
0818 ...Repeated for Digital Counter 4
0820 ...Repeated for Digital Counter 5
0828 ...Repeated for Digital Counter 6
0830 ...Repeated for Digital Counter 7
0838 ...Repeated for Digital Counter 8
FlexStates (Read Only)
0900 FlexState Bits (16 items) 0 to 65535 --- 1 F001 0
Element States (Read Only)
1000 Element Operate States (64 items) 0 to 65535 --- 1 F502 0
User Displays Actuals (Read Only)
1080 Formatted user-definable displays (16 items) --- --- --- F200 (none)
Modbus User Map Actuals (Read Only)
1200 User Map Values (256 items) 0 to 65535 --- 1 F001 0
Direct Analog Input and Output Settings (Read/Write) (32 Modules)
1320 Direct Analog Output 1 Value 0 to 65535 --- 1 F600 0
1321 Direct Analog Output 1 Deadband 0 to 1000000000 --- 0.001 F060 1000000
1323 Direct Analog Output 1 Trigger 0 to 4294967295 --- 1 F300 0
1325 Direct Analog Input 1 Device 0 to 16 --- 1 F001 0
1326 Direct Analog Input 1 Number 0 to 32 --- 1 F001 0
1327 Direct Analog Input 1 Units --- --- --- F207 (none)
1329 Direct Analog Input 1 Default Value –1000000000 to
1000000000
--- 0.001 F060 1000
132B Direct Analog Input 1 Mode 0 to 1 --- 1 F491 0 (Default Value)
132C Direct Analog Input 1 PU Base 1 to 2000000 --- 1 F003 1
132E ...Repeated for Direct Analog Inputs and Output 2
133C ...Repeated for Direct Analog Inputs and Output 3
134A ...Repeated for Direct Analog Inputs and Output 4
1358 ...Repeated for Direct Analog Inputs and Output 5
1366 ...Repeated for Direct Analog Inputs and Output 6
1374 ...Repeated for Direct Analog Inputs and Output 7
1382 ...Repeated for Direct Analog Inputs and Output 8
1390 ...Repeated for Direct Analog Inputs and Output 9
139E ...Repeated for Direct Analog Inputs and Output 10
13AC ...Repeated for Direct Analog Inputs and Output 11
13BA ...Repeated for Direct Analog Inputs and Output 12
13C8 ...Repeated for Direct Analog Inputs and Output 13
13D6 ...Repeated for Direct Analog Inputs and Output 14
13E4 ...Repeated for Direct Analog Inputs and Output 15
13F2 ...Repeated for Direct Analog Inputs and Output 16
1400 ...Repeated for Direct Analog Inputs and Output 17
140E ...Repeated for Direct Analog Inputs and Output 18
Table B–10: MODBUS MEMORY MAP (Sheet 6 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT