B-16 N60 Network Stability and Synchrophasor Measurement System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
1603 Field Shared Input States 0 to 65535 --- 1 F500 0
1604 Field Shared Input Channel States 0 to 65535 --- 1 F500 0
1605 Field Shared Input Test States 0 to 65535 --- 1 F500 0
1606 Field Shared Output Operand States 0 to 65535 --- 1 F500 0
1607 Field Latching Output Open Operand States 0 to 65535 --- 1 F500 0
1608 Field Latching Output Close Operand States 0 to 65535 --- 1 F500 0
1609 Field Latching Output Open Driver States 0 to 65535 --- 1 F500 0
160A Field Latching Output Close Driver States 0 to 65535 --- 1 F500 0
160B Field Latching Output Physical States 0 to 65535 --- 1 F500 0
160C Field Unit Online/Offline States 0 to 65535 --- 1 F500 0
160D Field RTD Input Trouble States 0 to 65535 --- 1 F500 0
160E Field Transducer Input Trouble States 0 to 65535 --- 1 F500 0
Ethernet Fibre Channel Status (Read/Write)
1610 Ethernet Primary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet Secondary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
1612 Ethernet Tertiary Fibre Channel Status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data Logger Channel Count 0 to 16 channel 1 F001 0
1619 Time of Oldest Available Samples 0 to 4294967295 seconds 1 F050 0
161B Time of Newest Available Samples 0 to 4294967295 seconds 1 F050 0
161D Data Logger Duration 0 to 999.9 days 0.1 F001 0
Sensitive Directional Power Actuals (Read Only) (2 Modules)
1680 Sensitive Directional Power 1 Power
-2147483647 to 2147483647
W1F060 0
1682 Sensitive Directional Power 2 Power
-2147483647 to 2147483647
W1F060 0
Field Unit RTD Actuals (Read Only) (8 Modules)
16C0 Field RTD x Value -32768 to 32767 °C 1 F002 0
16C1 ...Repeated for module number 2
16C2 ...Repeated for module number 3
16C3 ...Repeated for module number 4
16C4 ...Repeated for module number 5
16C5 ...Repeated for module number 6
16C6 ...Repeated for module number 7
16C7 ...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 Modules)
16C8 Field Transducer x Value -32.768 to 32.767 --- 0.001 F004 0
16CA ...Repeated for module number 2
16CC ...Repeated for module number 3
16CE ...Repeated for module number 4
16D0 ...Repeated for module number 5
16D2 ...Repeated for module number 6
16D4 ...Repeated for module number 7
16D6 ...Repeated for module number 8
Frequency Rate of Change Actuals (Read Only) (4 Modules)
16E0 Frequency Rate of Change 1 -327.67 to 327.67 Hz/s 0.01 F002 0
16E1 Reserved (3 items) 0 to 65535 --- 1 F001 0
16E4 ...Repeated for Frequency Rate of Change 2
16E8 ...Repeated for Frequency Rate of Change 3
16EC ...Repeated for Frequency Rate of Change 4
Source Current (Read Only) (6 Modules)
1800 Source 1 Phase A Current RMS 0 to 999999.999 A 0.001 F060 0
1802 Source 1 Phase B Current RMS 0 to 999999.999 A 0.001 F060 0
1804 Source 1 Phase C Current RMS 0 to 999999.999 A 0.001 F060 0
1806 Source 1 Neutral Current RMS 0 to 999999.999 A 0.001 F060 0
1808 Source 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT