GE Multilin N60 Network Stability and Synchrophasor Measurement System B-41
APPENDIX B B.4 MEMORY MAPPING
B
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7045 Phase Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7047 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7048 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7049 ...Repeated for Phase Overvoltage 2
7052 ...Repeated for Phase Overvoltage 3
Disconnect (Breaker) Switch (Read/Write setting) (24 Modules)
74A0 Disconnect Switch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
74A1 Disconnect Switch 1 Name --- --- --- F206 “SW 1"
74A4 Disconnect Switch 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
74A5 Disconnect Switch 1 Open 0 to 4294967295 --- 1 F300 0
74A7 Disconnect Switch 1 Block Open 0 to 4294967295 --- 1 F300 0
74A9 Disconnect Switch 1 Close 0 to 4294967295 --- 1 F300 0
74AB Disconnect Switch 1 Block Close 0 to 4294967295 --- 1 F300 0
74AD Disconnect Switch 1 Phase A / Three-pole Closed 0 to 4294967295 --- 1 F300 0
74AF Disconnect Switch 1 Phase A / Three-pole Opened 0 to 4294967295 --- 1 F300 0
74B1 Disconnect Switch 1 Phase B Closed 0 to 4294967295 --- 1 F300 0
74B3 Disconnect Switch 1 Phase B Opened 0 to 4294967295 --- 1 F300 0
74B5 Disconnect Switch 1 Phase C Closed 0 to 4294967295 --- 1 F300 0
74B7 Disconnect Switch 1 Phase C Opened 0 to 4294967295 --- 1 F300 0
74B9 Disconnect Switch 1 Operate Time 0 to 65.535 s 0.001 F001 70
74BA Disconnect Switch 1 Alarm Delay 0 to 65.535 s 0.001 F003 0
74BC Disconnect Switch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
74BD Reserved (2 items) --- --- --- --- ---
74BF ...Repeated for module number 2
74DE ...Repeated for module number 3
74FD ...Repeated for module number 4
741C ...Repeated for module number 5
743B ...Repeated for module number 6
755A ...Repeated for module number 7
7579 ...Repeated for module number 8
7598 ...Repeated for module number 9
75B7 ...Repeated for module number 10
75D6 ...Repeated for module number 11
75F5 ...Repeated for module number 12
7614 ...Repeated for module number 13
7633 ...Repeated for module number 14
7652 ...Repeated for module number 15
7671 ...Repeated for module number 16
7690 ...Repeated for module number 17
76AF ...Repeated for module number 18
76CE ...Repeated for module number 19
76ED ...Repeated for module number 20
770C ...Repeated for module number 21
772B ...Repeated for module number 22
774A ...Repeated for module number 23
7769 ...Repeated for module number 24
Thermal Overload Protection (Read/Write Settings) (2 Modules)
7788 Thermal Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7789 Thermal Protection 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
778A Thermal Protection 1 Base Current 0.2 to 3 pu 0.01 F001 80
778B Thermal Protection 1 K Factor 1 to 1.2 --- 0.05 F001 110
778C Thermal Protection 1 Trip Time Constant 0 to 1000 min. 1 F001 45
778D Thermal Protection 1 Reset Time Constant 0 to 1000 min. 1 F001 45
Table B–10: MODBUS MEMORY MAP (Sheet 33 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT