GE Multilin N60 Network Stability and Synchrophasor Measurement System B-51
APPENDIX B B.4 MEMORY MAPPING
B
9993 Teleprotection Local Relay ID 0 to 255 --- 1 F001 0
9994 Teleprotection Terminal 1 ID 0 to 255 --- 1 F001 0
9995 Teleprotection Terminal 2 ID 0 to 255 --- 1 F001 0
9996 Reserved (10 items) 0 to 1 --- --- F001 0
9A00 Teleprotection Input 1-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9A10 Teleprotection Input 2-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9A20 Teleprotection Output 1-n Operand (16 items) 0 to 4294967295 --- 1 F300 0
9A40 Teleprotection Output 2-n Operand (16 items) 0 to 4294967295 --- 1 F300 0
Teleprotection Channel Tests (Read Only)
9AA0 Teleprotection Channel 1 Status 0 to 2 --- 1 F134 1 (OK)
9AA1 Teleprotection Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
9AA2 Teleprotection Channel 2 Status 0 to 2 --- 1 F134 1 (OK)
9AA3 Teleprotection Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
9AA4 Teleprotection Network Status 0 to 2 --- 1 F134 2 (n/a)
9AAF Teleprotection Channel 1 Input States 0 to 1 --- 1 F500 0
9AB0 Teleprotection Channel 2 Input States 0 to 1 --- 1 F500 0
9AC0 Teleprotection Input 1 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
9AD0 Teleprotection Input 2 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
VT Fuse Failure Settings (Read/Write) (6 Modules)
A09A VT Fuse Failure Function 0 to 1 --- 1 F102 0 (Disabled)
A09B VT Fuse Failure Neutral Wire Open Function 0 to 1 --- 1 F102 0 (Disabled)
A09C VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup 0 to 3 pu 0.001 F001 100
A09D ...Repeated for module number 2
A0A0 ...Repeated for module number 3
A0A3 ...Repeated for module number 4
A0A6 ...Repeated for module number 5
A0A9 ...Repeated for module number 6
VT Fuse Failure Actual Values (Read Only) (6 Modules)
A0AC VTFF x V0 3rd harmonic 0 to 999999.999 V 0.001 F060 0
A0AE ...Repeated for module number 2
A0B0 ...Repeated for module number 3
A0B2 ...Repeated for module number 4
A0B4 ...Repeated for module number 5
A0B6 ...Repeated for module number 6
Summator Settings (Read/Write) (6 Modules)
A0C0 Summator 1 function 0 to 1 --- 1 F102 0 (Disabled)
A0C1 Summator 1 input mode 0 to 1 --- 1 F515 0 (Signed)
A0C2 Summator 1 hold 0 to 4294967295 --- 1 F300 0
A0C4 Summator 1 pickup –2000000 to 2000000 --- 0.001 F004 1000000
A0C6 Summator 1 hysteresis 0.1 to 50 % 0.1 F001 30
A0C7 Summator 1 input 0 to 4294967295 --- 1 F600 0
A0CD Summator 1 scale factor –2000 to 2000 --- 0.000001 F004 1000000
A0D9 Summator 1 position selector 0 to 4294967295 --- 1 F300 0
A0E5 Summator 1 units --- --- --- F207 (none)
A0E7 Summator 1 events 0 to 1 --- 1 F102 0 (Disabled)
A0E8 Summator 1 per-unit base 1 to 2000000 --- 1 F004 1
A0EA ...Repeated for summator 2
A114 ...Repeated for summator 3
A13E ...Repeated for summator 4
A168 ...Repeated for summator 5
A192 ...Repeated for summator 6
Selector Switch Actual Values (Read Only)
A210 Selector switch 1 position 1 to 7 --- 1 F001 0
A211 Selector switch 2 position 1 to 7 --- 1 F001 1
Table B–10: MODBUS MEMORY MAP (Sheet 43 of 70)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT