16 
  NX-6V2 Control 
Segment 2: 
1 =  On enables the LED Extinguish feature. 
2 =  On enables the Require Code for Bypassing feature. 
3 =  On enables the Zone Bypassed Sounder Alert feature. 
4 =  On enables the AC Power/Low Battery Sounder Alert feature. 
5 =  On enables Bypass toggle. 
6 =  On enables Silent Auto Arm. 
7 =  On enables the Automatic Instant feature. 
8 =  On enables Instant mode toggle.  (Applies to NX-1208E / NX-1248E keypads) 
 
Segment 3:   
1 =  On enables Opening and Closing reports. 
2 =  On enables Zone Bypass reporting. 
3 =  On enables Zone Restore reporting. 
4 =  On enables Zone Trouble reporting. 
5 =  On enables Zone Tamper reporting. 
6 =  On enables the Cancel reporting. 
7 =  On enables the Recent Closing report. 
8 =  On enables the Exit Error report. 
 
Segment 4: 
1 =  On enables Late to Close / Early to Open. 
2 =  On enables Auto Arm in Stay Mode. 
3 =  On disables the door delays in Night mode.  (Applies to NX-1208E / NX-1248E keypads) 
4 - 8 = Reserved. 
 
Segment 5: Reserved 
 
L  24  ENTRY / EXIT TIMERS  6 ............ numerical 
Location 24 is used to program the Entry/Exit times. There are 2 separate Entry/Exit times. 
 
Segment 1,   Entry time 1:   This is the entry time that will be used when a delay 1 zone type initiates an entry delay. Valid 
entries are 30-255 seconds.  
Segment 2,   Exit time 1:  This is the exit time that will be used for all zones designated as delay 1. Valid entries are 45-255 
seconds.  
Segment 3,  Entry time 2:  This is the entry time that will be used when a delay 2 zone type initiates an entry delay. Valid 
entries are 30-255 seconds.  
Segment 4,   Exit time 2:  This is the exit time that will be used for all zones designated as delay 2.  Valid entries are 45-255 
seconds. 
Segments 5 & 6 Reserved. 
 
 
XIII. DEFAULT ZONE TYPES (Configurations) 
Zones can be programmed to be one of thirty different zone types (configurations). Zone types 17 - 20 can be used for wireless or 
hardwired zones using European double EOL configuration. The default zone types are listed below. These zone types can be 
customized by programming locations 110-169. 
 
DATA  DESCRIPTION OF DEFAULT ZONE TYPES 
1  DAY ZONE - Instant when system is armed trouble zone when system is disarmed. 
2  24-HOUR AUDIBLE - Creates an instant yelping siren alarm regardless of the armed state of the control panel. 
3 
ENTRY/EXIT DELAY 1- A trip will start entry delay 1.  The lack of a trip during exit delay will enable the Automatic 
Bypass or Instant mode if so programmed. 
4 
FOLLOWER WITH AUTO- BYPASS DISABLED - This zone will be instant when the system is armed and no entry or 
exit delays are being timed. It is delayed during entry and exit delay 1 times. This zone will not automatically bypass even 
if enabled in Segment 1 of Location 23. 
5 
INTERIOR FOLLOWER WITH AUTO- BYPASS ENABLED - This zone will be instant when the system is armed and no 
entry or exit delay is being timed. It is delayed during entry and exit delay 1 times. This zone will automatically bypass if 
enabled in Segment 1 of Location 23. 
6  INSTANT - This zone creates an instant alarm whenever it is tripped and the Armed LED is on. 
7 
24-HOUR SILENT - Creates an instant silent alarm regardless of the armed state of the control panel. It will not display 
on the keypad. 
8 
FIRE - This zone will light the Fire LED and sound the temporal siren each time the zone is shorted. It will also rapidly 
flash the Fire LED indicating a trouble if the zone is open.