NX-6V2 Control    49 
MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS 
(Residential Fire, Residential Burglary, Commercial Burglary) 
•  The NetworX NX-6V2 panel is necessary to initiate Residential and Commercial installations. 
•  At least one compatible keypad is needed for all applications. 
•  At least one bell fixture is required for all applications, except Grade C Central Station.  For Grade A Local, the AD10-12 bell 
and Grade A bell housing shall be used. 
•  Commercial UL applications require #NX-003-C metal enclosure.  Supplied screws to be used. 
•  A minimum of two (2) keypads is required for Home Health applications and each keypad must be set to a unique address. 
•  The wireless devices are only UL listed for residential applications. 
•  The DACT shall be enabled for all commercial burglary applications. 
 
 
 
STANDBY TIME  TOTAL AUXILIARY 
CURRENT 
STANDBY BATTERY 
CAPACITY 
ALARM CURRENT 
24 hours  1.9 Amps  51 AH  600 mA 
  1.25 Amps  34 AH  1 Amp 
  600 mA  17 AH  1 Amp 
48 hours  900 mA  51 AH  1 Amp 
  600 mA  34 AH  1 Amp 
  300 mA  17 AH  1 Amp 
72 hours  600 mA  51 AH  1 Amp 
  400 mA  34 AH  1 Amp 
  200 mA  17 AH  1 Amp 
Calculations based on three 17-Amp batteries. 
 
 
 
K 
IMPORTANT! 
If separate power supplies are necessary to accommodate additional devices, safety standards require that each power 
supply be prominently marked with adequate instructions for removing all power from the unit. 
Dispose of used batteries according to the manufacturer’s instructions and/or local government authorities. 
Installation personnel should thoroughly read and understand the installation instructions and the users manuals for the panel 
and all the accessories to be included with the system before attempting to install a security system. 
 
 
WARNING! 
Replace only with Panasonic #LC12V4BP or Yuasa #NP4-12 battery. Observe polarity when installing a new battery. 
Installing the battery backwards may cause damage to the panel. There is a risk of explosion if the battery is replaced with an 
incorrect type. 
 
 
NOTE 
Electrical codes will vary depending upon the country and city where the system is installed. It is the installer’s responsibility 
to ensure that the electrical installation is safe and conforms to all applicable codes, laws, or regulations. Only qualified 
persons should connect this device to the mains supply.