GFK-2839B PAC8000* IO PROFINET Scanner User’s Manual–September 2017 47
Chapter 5. PROFINET Specifications
Release 2.00 of the PAC8000 PROFINET Scanner supports PROFINET v2.3 Class A
IO-Device with the clarifications listed below. For version-specific updates, refer to the
Important Product Information document provided with your module.
5.1 PROFINET Protocol Support
RTC Real time Cyclic Protocol: RT_CLASS_1 & RT_CLASS_2
RTA Real time Acyclic Protocol
DCP Discovery and Configuration Protocol
CL-RPC Connectionless Remote Procedure Call
LLDP Link Layer Discovery Protocol transmission only
MRP Client role only (Manager role not supported)
PTCP Precision Transparent Clock Protocol Line delay measurement only
5.2 Technical Data
API:
Single API (0) used.
Number of Application Relations
supported:
1 (Additional Supervisor-DA-AR allowed)
Number of System Redundancy
Application Relations (SR-AR) sets
supported
1
Maximum length of cyclic input
data:
1440 bytes
Maximum length of output data:
1440 bytes
Alarm Types:
Pull, Plug, PlugWrong
DCP:
Get/Set/Identify supported. Only All and Name Of
Station filters supported
Identification & Maintenance:
I&M0 only
Context Management:
by CL-RPC
Minimum cycle time:
1ms
Ethernet rate:
100 Mbit/s full duplex with auto-negotiation