GFK-2839B PAC8000* IO PROFINET Scanner User’s Manual–September 2017 9
1.3 PAC8000 PROFINET Scanner Specifications
PROFINET Version 2.3 Class A IO-Device
Redundantly controlled operation conforms to PROFINET V2.3 Type
S2 System Redundancy.
RX3i PLC CPU Version
Required
Firmware version 7.0 or later
Proficy Machine Edition
Version Required
Version 7.5 SIM 3 or later
V2.3 GSDML and Proficy Machine Edition/3rd-Party tools.
8515-BI-PN 4.5 Watts (5.5 Watts Max)
8516-BI-PN 6.0 Watts (7.2 Watts Max)
Length: 160.3mm (6.31”), Width: 128.3mm (5.05")
Thickness 47.78mm (1.88”)
8752-CA-NS : PAC8000 Node Service Carrier
Operating Temperature
Range
8515-BI-PN -40˚C to +70˚C
8516-BI-PN -40˚C to +70˚C
Horizontal DIN rail mounting.
Optimum orientation is when the carrier is mounted in a vertical plane
with field terminals for communication cables located below the
modules.
Number of Port
Connectors
8515-BI-PN : Two RJ-45
8516-BI-PN : Two SC-Duplex
USB Connector (for
firmware upgrades)
One Micro-B connector. USB 2.0 compliant running at full speed
(12 MHz)
PNS Status and Control
Bits
64 input status bits and 48 output control bits
I/O Data Update on the
PROFINET LAN
Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms
and 512ms (Recommended is 4 ms and above)
One. Supports Classless Inter-Domain Routing (CIDR)
Three. One per external port and one internal. External MAC addresses
are only used for specialized Ethernet protocols such as MRP or LLDP
I/O Station Maximum
Limits
Number of IO Modules per
Node
2880 bytes total
1440 bytes of input data
1440 bytes of output data
Configured using Proficy Machine Edition when used with a
PACSystems RX3i PROFINET Controller (PNC) module, as part of an
RX3i PROFINET network.
V2.3 GSDML file is available for import into 3
rd
-Party tools.
For product standards, general operating specifications, and installation requirements, refer
to the PAC8000 IO modules Manual, INM8200.pdf.