EasyManua.ls Logo

GE RSTi-EP - 3.9 Parameter Overview

GE RSTi-EP
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. Detailed Descriptions of EP-19xx Modules
36 RSTi-EP Functional Safety Manual GFK-2956A
5.5.3 Specifications EP-1922
System data
Data
Process and diagnostic data depend on the network adapter used
(refer to the table in the section, Data Width of EP-19xx Modules)
Interface
RSTi-EP system bus
System bus transfer rate
48 Mbps
Safety-related data per EN ISO 13849 (Regard the entire safety chain)
Achievable safety level
PLe and Cat. 4
DC (Diagnostic Coverage)
99%
MTTFd (Mean Time To Failure dangerous)
> 100 years
Safety-related data per EN 62061 (Regard the entire safety chain)
Achievable safety level
SILCL3
PFH (Probability of Failure in 1/h)
6.27 x 10
-9
Fault reaction time
10 s
Safety-related data per EN 61508 (Regard the entire safety chain)
Achievable safety level
SIL3
PFH (Probability of Failure per Hour)
6.27 x 10
-9
HFT (Hardware Fault Tolerance)
1
SSF (Safe Failure Fraction)
98.58%
Presumed lifecycle time
20 years
Prooftest interval
No prooftest needed within the life cycle
Classification acc. To EN 61508-2:2010
Type B
Inputs
Safety inputs
2 x 2 channel
Input type
Type 3 as per IEC 61131-2
Inputs for start function
2 (manual start and auto start)
Input type
Type 3 as per IEC 61131-2
Outputs
Safety output (OSSD)
1
Output current
8 A (not for capacitive load)
Overload protection
excess temperature proof and overload-proof, short circuit proof
with external fuse
Turn-off time
20 ms
Turn-on time
< 2 s
Output SS1
1
Output current
0.5 A, overload behaviour as per IEC 61131-2
Overload protection
excess temperature proof and overload-proof, short circuit proof
with external fuse
Auxiliary outputs
3 x 2
Output current
max. 10 A (only to support the inputs dedicated inputs)

Table of Contents

Other manuals for GE RSTi-EP

Related product manuals