Chapter 7. Example Applications
GFK-2956A November 2017 45
7.3 Dual-channel Emergency Stop and Cable-pull Switch
Monitoring
Achievable safety rating
Cat. 4
DIN EN ISO 13849-1
PLe
DIN EN ISO 13849-1
SIL3
IEC 62061/61508
Stop category
0
EN 60204-1
Features
Dual-channel monitoring
Cross-connection detection
Start buton
Monitoring of external contactors (EDM)
Safety sensor/operating
mechanism
Emergency stop button
Cable-pull switch, latching
Notes
Manual reset
Autostart is possible if the NC circuits from
K3 and K4 are attached to 3.3 and 3.4.
Note: All example applications shown are proposals without warranty. In any case the operator has
to perform a safety review of the entire site.
When the emergency stop button is pushed or the cable-pull switch is activated, the EP-19xx
switches off the 24 V supply for the modules (switchable modules refer to the section, General
Contact Information) within the safety segment and thus also contactors K3 and K4. The failure of a
switching element in the emergency stop button or the cable-pull switch as well as a cross-circuit in
their supply lines does not result in the failure of the emergency stop mechanism and is detected
within the fault-reaction time.
The EP-19xx module switches on the 24-V supply for the modules within the safety segment if:
Emergency button is unlocked
Cable-pull switch is unlocked
Feedback circuit (NC contacts of K3 and K4) is closed
Start push button has been pushed and released again
Contactors K3 and K4 are controlled by the PLC and can switch on as soon as the EP-19xx has
switched on the 24-V supply.