EasyManua.ls Logo

GE RSTi-EP - Dual-Channel Safety Door Monitoring, Spring-Operated Interlock, Controlled Shutdown with Manual Reset and Emergency Stop

GE RSTi-EP
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7. Example Applications
GFK-2956A November 2017 61
7.11 Dual-channel Safety Door Monitoring, Spring-operated
Interlock, Controlled Shutdown with Manual Reset and Emergency
Stop
Achievable safety rating
Cat. 4
DIN EN ISO 13849-1
PLe
DIN EN ISO 13849-1
SIL3
IEC 62061/61508
Stop category
0
EN 60204-1
Features
Dual-channel monitoring
Cross-connection detection
Manual reset
Monitoring of external contactors (EDM)
Safety sensor/operating
mechanism
Emergency stop button
Position switch with interlock
Manual unlocking
Notes
Exclusion of the fault Interruption or
releasing of the activator, error in the
safety interlock
As soon as the enabling on the
frequency converter is withdrawn, the
converter must execute a controlled
shutdown
Note: All example applications shown are proposals without warranty. In any case the operator has
to perform a safety review of the entire site.
When the emergency stop button is pushed, the EP-19xx switches off the 24-V supply for the
modules (switchable modules refer to the section, General Contact Information) within the safety
segment and thus also contactors K3 and K4. The failure of a switching element in the emergency
stop button or the safety door contact as well as a cross-circuit in their supply lines does not result in
the failure of the emergency stop mechanism and is detected within the fault-reaction time.
After pressing the stop button and the delay time set in the EP-1922, the spring-operated interlock
can be activated with the unlock button and the safety door can be opened. When the power supply
is turned off, the safety door cannot be opened if the locking mechanism is engaged. We recommend
using switches with mechanical unlocking capabilities.
The EP-19xx switches on the 24-V supply for modules within the safety segment if:
Emergency button is unlocked
Safety door is closed
Locking mechanism is engaged
Feedback circuit (NC contacts of K3 and K4) is closed
Start push button has been pushed and released again
Contactors K3 and K4 are controlled by the PLC and can switch on as soon as the EP-19xx has
switched on the 24-V supply.

Table of Contents

Other manuals for GE RSTi-EP

Related product manuals