GFK-2956A November 2017 13
4.1 Switch-off Delay Time
The turn-off time of a EP-19xx module is 20 ms, caused by the hardware and firmware delay time.
The time required until the output voltage even of the last switchable module of a safety segment is
below 5 V, can be calculated as follows:
Switch off delay [ms] =
Turn-off time of a EP-19xx module
+ Sum of all modules’ hardware delay
Switch-off Delay and Current Consumption
4.2 Operation With and Without Test Pulses
All safe power-feed modules provide a test pulse evaluation, so that the highest safety levels can be
achieved (see technical data).
Example of Operation with Test Pulses