• Dual-channel monitoring
• Cross-connection detection
• Automatic reset
• Monitoring of external contactors (EDM)
Note: All example applications shown are proposals without warranty. In any case the operator has
to perform a safety review of the entire site.
When the emergency stop button is pushed or the safety door is opened, the EP-19xx switches off
the 24-V supply for the modules (switchable modules refer to the section, General Contact
Information) within the safety segment and thus also contactors K3 and K4. The failure of a switching
element in the emergency stop button or the safety door contacts as well as a cross-circuit in their
supply lines does not result in the failure of the emergency stop mechanism and is detected within
the fault-reaction time.
The EP-19xx switches on the 24-V supply for the following modules* within the safety segment if:
• Emergency button is unlocked
• Safety door is closed
• Feedback circuit (NC contacts of K3 and K4) is closed
Contactors K3 and K4 are controlled by the PLC and can switch on as soon as the EP-19xx module
has switched on the 24-V supply. To reset the system, press the reset button within 0.1 to 2 sec after
switching on the power supply, even when automatic reset is used.