Chapter 7. Example Applications
GFK-2956A November 2017 57
7.9 Dual-channel Safety Door Monitoring, Magnetically Operated
Interlock with Manual Reset and Emergency Stop
Achievable safety rating
Cat. 4
DIN EN ISO 13849-1
PLe
DIN EN ISO 13849-1
SIL3
IEC 62061/61508
Stop category
0
EN 60204-1
Features
Dual-channel monitoring
Cross-connection detection
Automatic reset
Monitoring of external contactors (EDM)
Off-delay via PLC
Safety sensor/operating
mechanism
Emergency stop button
Position switch with interlock
Notes
Exclusion of the fault Interruption or
releasing of the activator, error in the
safety interlock
The PLC must activate the interlock
directly after the safety door is closed
Note: All example applications shown are proposals without warranty. In any case the operator has
to perform a safety review of the entire site.
When the emergency stop button is pushed, the EP-19xx switches off the 24-V supply for the
modules (switchable modules refer to the section, General Contact Information) within the safety
segment and thus also contactors K3 and K4. The failure of a switching element in the emergency
stop button or the safety door contact as well as a cross-circuit in their supply lines does not result in
the failure of the emergency stop mechanism and is detected within the fault-reaction time.
A stop is performed by switching off K3 and K4 via the PLC. The door can be opened when the PLC
releases the interlock.
The EP-19xx switches on the 24-V supply for modules within the safety segment if
Emergency button is unlocked
Safety door is closed
PLC has activated and engaged the interlock
Feedback circuit (NC contacts of K3 and K4) is closed
Start push button has been pushed and released again
Contactors K3 and K4 are controlled by the PLC and can switch on as soon as the EP-19xx has
switched on the 24-V supply.