GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual TLE Series 160 - 500 UL S2B
Code Message Description
4604 COMMAND IEMi ON
The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will
run in IEMi Operation Mode.
The IEMi Operation Mode has been disabled or the
programmed time is expired.
4606 eBoost/IEMi ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
4607 eBoost/IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.
4609 eBoost INHIBITED - LOW LOAD
eBoost™ Operation Mode inhibited due to minimal
load not reached.
4699 BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
- No Utility Rectifier or Bypass.
- Battery not fully charged.
- Load is below 10% or above 80%.
Test is postponed for 1 week.
Inverter can be started or shut-down by remote
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
4798 SERVICE KEY ACTIVATED
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
The Service Key validity period has expired.