7.2.4 Restore to normal operation after EPO - Emergency Power Off with Load not
supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
“Q1 - UPS Output switch” MUST BE CLOSED.
“External Battery Protections” MUST BE DISCONNECTED and the CB3 -External
Battery switchoption” MUST BE OPEN.
View of the Synoptic Diagram after
performed the command “EPO -Emergency
Power Off”, with LOAD NOT SUPPLIED.
1. Restore the “EPO -Emergency Power Off” button.
Press “MUTE” key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the “Inverter OFF” command.
Perform the “Inverter OFF” command from
the screen: Commands 1 / Inverter / OFF.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the
LED 1
(Rectifier) remains lit.