7.2 PROCEDURES SINGLE TLE Series 160 - 500 FUNCTIONING AS FREQUENCY
CONVERTER
When the TLE Series 160 - 500 functions as a Frequency Converter, the Automatic Bypass function is
disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shut-down for maintenance purposes, also the Load must be
shut-down or disconnected.
7.2.1 Initial Start-up of the TLE Series 160 - 500 as frequency converter
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external
isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
Open the front door and make sure that:
• All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
• The safety screens are fixed in their position.
• The switches Q1 and CB3 (option) are open (Pos. O) and the “External Battery Protections” must be
open (Pos. O).
TLE Series 160 – 200 -225 - 250
TLE Series 300 – 400 - 500
The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your GE Service Center.