Critical Power
Modifications reserved
Page 71/91
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
User Manual TLE Series 160 - 500 UL S2B
3. Insert the Inverter performing the command Inverter ON".
Perform the “Inverter ON command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
LOAD SUPPLIED BY INVERTER.
END OF PROCEDURE