Module shutdown
Module shutdown
Load Off command for a single UPS.
NOTE !
This command will immediately disconnect the Load.
Module shutdown cannot disconnect the UPS from the Load with “Q2 -
Manual Bypass switch” (only if provided by customer) closed.
For the RPA Parallel System
In an RPA Parallel System, the “Module shutdown” command disconnects the
Load to the selected unit only (Q1UPS Output switch” closed).
Module shutdown RESET
“Module shutdown” restore command for an individual UPS.
Led Module shutdown status
Shows the “Module shutdown” status: ACTIVE / NOT ACTIVE
System shutdown
System shutdown
Load Off command for an RPA Parallel System.
NOTE !
This command will immediately disconnect the Load.
System shutdown cannot disconnect the RPA Parallel System from the
Load with “Q2 - Manual Bypass switch (only if provided by customer) closed.
For the RPA Parallel System
If System shutdown is pressed on one unit connected to the Parallel Bus (Q1
UPS Output switch” closed), all the units are separated from the Load.
System shutdown RESET
“System shutdown restore command for a RPA Parallel System.
For the RPA Parallel System
The “System shutdown resetmust be done only on one unit connected to the
Parallel Bus (Q1 UPS Output switch” closed).
Led System shutdown status
Shows the “System shutdown” status: ACTIVE / NOT ACTIVE
Booster
Only for GE Service Center.