4-44
5) 03-11=
4
. RY1 will be on while Output Freq. > Frequency Detection Level (03-13).
When Output Freq.> (03-13), Relay output will be ON.
FWD
REV
Setting Freq.
Setting Freq.
Output Freq.
Output Freq.
RUN RUN
ON ON
Run Command
Relay Output
(03-13)
(03-13)
Hz
Time
0
6) 03-11=
5
. RY1 will be on while Output Freq. < Frequency Detection Level (03-13).
Output Current Detection Level
0.1~999.9
A
Output Current Detection Period
0.1~10.0
s
03-11=
13】.RY1 will be on as soon as the output current value > Output current
detection level (03-15).
03-15: Setting range (0.1~15.0 Amps) as required according to the rated motor current.
03-16: Setting range (0.1~10.0) unit: seconds.
When Output Freq.< (03-13), Relay output will be ON.
FWD
REV
Setting Freq.
Setting Freq.
Output Freq.
Output Freq.
RUN RUN
ON
Run Command
Relay Output
(03-13)
(03-13)
Hz
Time
0