What does SC short circuit mean on gefran VDI100-3110-KBX-4?
U
ularsonAug 31, 2025
An SC (Short Circuit) error on your Gefran Inverter can be caused by a short circuit or ground fault; check the motor wiring. It could also indicate a damaged motor (insulation); in that case, disconnect the motor and try running the inverter. Wire damage or deterioration can also cause this error; disconnect the motor and try running the inverter.
D
Dr. Patricia GardnerAug 29, 2025
Why am I getting a UV Under voltage error on my gefran VDI100-3110-KBX-4 Inverter?
S
Sarah RussellAug 30, 2025
If your Gefran Inverter is showing a UV (Under Voltage) error, it could be due to several reasons. The input voltage might be too low, so check the input voltage. There might be an input phase loss, so check the input wiring. The acceleration time might be set too short, so increase the acceleration time. Input voltage fluctuation could also be the cause, so check the power source. The pre-charge contactor could be damaged, so replace the pre-charge contactor. Also, the DC bus voltage feedback signal value might be incorrect, so replace the control board or the entire inverter.
A
Amanda Nelson DDSAug 28, 2025
What does OL2 Inverter overload mean on my Gefran Inverter?
M
michaelbennettAug 29, 2025
If your Gefran Inverter displays an OL2 (Inverter Overload) error, it could be due to a few reasons. The voltage setting in V/f mode might be too high, causing over-excitation of the motor; check the V/f curve. The inverter rating might be too small; replace the inverter with a larger rating. Finally, the load might be too heavy; check and reduce the motor load, and check the operation duty cycle.
M
Michelle MosesAug 27, 2025
What causes an OL1 Motor overload error on a gefran VDI100-3110-KBX-4?
M
murphybrandonAug 27, 2025
If your Gefran Inverter displays an OL1 (Motor Overload) error, it could be due to a few reasons. The voltage setting in V/f mode might be too high, causing over-excitation of the motor; check the V/f curve. The motor rated current setting might be incorrect; check the motor rated current. Finally, the load might be too heavy; check and reduce the motor load, and check the operation duty cycle.
A
annemaddenAug 27, 2025
What causes a GF Ground fault error on my Gefran Inverter?
T
Timothy FoleyAug 27, 2025
If you're seeing a GF (Ground Fault) error on your Gefran Inverter, it could be due to several reasons. The motor might be damaged (insulation failure), so replace the motor. There could also be damage or deterioration to the wiring, so check the motor wiring. A defect in the inverter's DCCT sensors could also cause this; check the resistance between the cables and ground. Also, try reducing the carrier frequency.
K
Kristina ColemanAug 25, 2025
Why does my gefran VDI100-3110-KBX-4 show an OCA over current error?
H
Herbert AllenAug 26, 2025
If your Gefran Inverter is showing an OCA (Over Current) error, it might be because the acceleration time is too short; try setting a longer acceleration time. The motor might be too big for the inverter; if so, consider changing to a larger inverter. There could also be a short circuit between the motor winding and shell, so examine the motor. Another potential cause is a short circuit between the motor wire and ground; in this case, check the wire. Finally, a broken IGBT module can trigger this error; if you suspect this, replace the IGBT module, and please contact Gefran Technical Assistance.
K
Kelli BlackAug 25, 2025
What to do if my Gefran Inverter displays an OC over current error?
L
Luke ScottAug 25, 2025
An OC (Over Current) error on your Gefran Inverter can occur if the acceleration or deceleration time is too short; try extending these times. It can also happen if there's a contactor on the inverter output side, so check the motor wiring. If the motor is either a special type, or larger than the inverter's rated value, disconnect the motor and try running the inverter. A short circuit or ground fault could also be the cause; in this case, disconnect the motor and attempt to run the inverter.