- 38 -
COMMISSIONING
- For commissioning with the summer setting:
• For the FCX models:
. Stop the boiler using the Stop/Start switch
(item no. 1),
• For the FCX + domestic hot water production
tank models or other type:
. press the Summer/Winter switch (item
no.
2) - Summer position,
. set the tank domestic hot water thermostat
to the required temperature,
. position the boiler temperature thermostat
(item no. 3) to the minimum,
. set the mixer valve (fig. 2, item no. 5) to po-
sition "0".
In the summer it is advisable to operate
the heating pump for several minutes to
avoid any risks of fouling (see §
section 4 - page 41).
(When the boiler is equipped with an
electronic regulator, this function is
performed automatically).
6.2 - Commissioning procedure - with
regulator
See the regulator technical instructions for tempera-
ture control.
Set the boiler temperature thermostat
(item no. 3) to maximum.
6.3 - Commissioning the oil burner
- When commissioning the oil burner for the first ti-
me:
• check that the smoke spot number does not
exceed 0.5 (BACHARACH control),
• check the CO2 rate - 11.5 to 12.5 %, CO < 100
ppm (watch out for secondary air inlets),
• check the temperature of the combustion pro-
ducts (under 120 °C).
Remark:
- The burners are preset in the factory for the ba-
lanced flue model FCX. Nevertheless the air and
oil inlet settings must be checked systematically
on commissioning and after all maintenance ope
-
rations on the burner by testing the opaqueness
of the flue gasses and of the % CO2 - See the
burner technical instructions.
- For the installed flue model FCX boilers the air
setting must be readjusted to obtain the recom
-
mended CO2/CO rate.
- The pressure of the burner oil pump shall be
checked or adjusted via the hole ( 37) after remo
-
ving the plug.
1
-
+
3
FCX-48-0
Fig. 59
!
!
Models FCX 22 C FCX 30 C
GEMINOX
oil burner
ST 108 FUV ST 120 RV
Preset
Max
power
Presetting
at the
maximum
power
Heat flow kW 21,7 23,8 31,5
Pump
pressure
bar 12 14 14
Spray nozzle 0,50 80°H 0,65 60°S
Oil inlet setting
2,5
7
Air setting
(FCX balanced flue
outlet)
6,5 9,5
16
37
FCX-79-0
Fig. 60