Online Technical Support:
support.mobilelinkgen.com
MobileLink:
mobilelinkgen.com
855-436-8439—United States
844-843-9436—Canada
SAVE THIS MANUAL FOR FUTURE REFERENCE
004388
Mobile Link™
Wi-Fi
®
Remote Monitoring
Installation and User Manual
(000209b)
WARNING
Loss of life. This product is not intended to
be used in a critical life support application.
Failure to adhere to this warning could result
in death or serious injury.

Questions and Answers

  • T
    timothy91Aug 18, 2025
    What to do if the LED is off on my Generac Power Systems Wireless Router?
    • A
      andrewdodsonAug 18, 2025
      If the LED on your Generac Power Systems Wireless Router is off, start by checking the 5 Amp fuse located on the yellow harness wire. Also, make sure that the connector on the Wi-Fi module harness is properly seated in the socket on the controller. Check your Wi-Fi router and reset it if necessary. If the connection is poor, consider adding a repeater to boost the signal. Ensure the unit is activated by visiting www.ActivateGen.com.
  • D
    daltondebraAug 20, 2025
    Why is my Generac Power Systems Wireless Router Wi-Fi module not connecting to home network?
    • G
      gbarryAug 20, 2025
      If your Generac Power Systems Wireless Router's Wi-Fi module isn't connecting to your home network, it might be due to a change with your ISP, a power outage, or a replaced network router. If your ISP has changed or your network router has been replaced, follow the reconnection process. If a power outage has occurred, wait for the utility or backup power source to return.
  • J
    Jeremy MilesAug 23, 2025
    How to fix LED flashing on Generac Power Systems Wireless Router?
    • S
      Shawn ScottAug 23, 2025
      If the LED is flashing rapidly (approximately 2-3 times per second) on your Generac Power Systems Wireless Router, it could be due to a low RSSI, incorrect wireless password, or an incorrectly entered SSID. Check the signal strength and boost the network signal as needed. If the wireless password or SSID was entered incorrectly, restart the connection process after verifying the information.
  • S
    Stacey HarrisAug 26, 2025
    What to do if LED is steadily on on Generac Power Systems Wireless Router?
    • H
      hglassAug 26, 2025
      If the LED on your Generac Power Systems Wireless Router is steadily on, the Wi-Fi module might be locked up. To resolve this, navigate to [Sub Menus]–[Edit]–[WiFi]–ENABLE WIFI. Select NO, then YES, to restart the Wi-Fi module.
  • V
    Vanessa BatesAug 28, 2025
    What to do if the Cellular Network LED (B) is flashing on my Generac Power Systems Measuring Instruments?
    • R
      Randall OlsonAug 28, 2025
      If the Cellular Network LED (B) on your Generac Power Systems Measuring Instruments is flashing or off, it could be due to a variable or weak connection to the cellular network. Try the following: * Reset the connector at the generator controller and the Mobile Link cellular unit. * Ensure the external antenna is tightly attached to the Mobile Link cellular unit. * Consider replacing the cable. In some cases, the issue may resolve itself within 10 minutes. If the LED continues to flash, consider purchasing an extender antenna or contacting Customer Support. Keep in mind that cellular coverage can be intermittent.
  • L
    Lance CuevasAug 30, 2025
    Why is the Server Connection LED (D) off on my Generac Power Systems Measuring Instruments?
    • J
      Jeffrey HernandezAug 30, 2025
      If the Server Connection LED (D) is off on your Generac Power Systems Measuring Instruments, the Mobile Link cellular unit may not be connected to the Mobile Link server. This could be because the server is down, so wait for a server response. Alternatively, the controller might be unsupported; verify it is a Nexus, Evolution 1.0, or Evolution 2.0. It is also possible that the Mobile Link cellular unit is in “Suspended” mode, in which case you should contact Mobile Link Customer Service for assistance at (US) 1-855-436-8439 or (CAN) 1-844-843-9436.
  • R
    Rachel HunterSep 2, 2025
    What does it mean when the Connection to Controller LED (C) is flashing on Generac Power Systems Measuring Instruments?
    • A
      annette36Sep 2, 2025
      If the Connection to Controller LED (C) is flashing on your Generac Power Systems Measuring Instruments, the generator controller is communicating with the Mobile Link cellular unit, but has not yet been identified. To resolve this, verify that the controller is compatible with the Mobile Link cellular unit (Nexus, Evolution 1.0, and Evolution 2.0). Also, ensure that all harness connections between the Mobile Link cellular unit and the generator controller are correct and tight. The light will turn solid when communications are established.
  • K
    Kristen RamosSep 4, 2025
    How to troubleshoot all LEDs off on Generac Power Systems Measuring Instruments?
    • E
      Eugene HoldenSep 5, 2025
      If all the LEDs are off on your Generac Power Systems Measuring Instruments, it indicates that there is no power to the Mobile Link cellular unit. Inspect the wire harness connections. For Evolution 2.0 controllers, the Mobile Link cellular unit receives power directly from the controller. For non-Evolution 2.0 controllers, it receives power from the battery connections. Also, verify the harness is correctly connected to the battery and reset the connector to the Mobile Link cellular unit.
  • S
    Steven BarnesSep 7, 2025
    What to do if Connection to Controller LED (C) is off on Generac Power Systems Measuring Instruments?
    • E
      edwinpotterSep 7, 2025
      If the Connection to Controller LED (C) is off on your Generac Power Systems Measuring Instruments, it could indicate that the Mobile Link cellular unit is not connected to the generator controller. Try resetting the Mobile Link cellular unit wire harness to the generator controller and verify that all harness connections between the unit and the generator controller are correct. Also, wait a few moments, as Mobile Link will not attempt to communicate with the controller for approximately 15 seconds upon initial startup. Inspect the wire harness and battery connections (if applicable) and tighten if necessary.
  • B
    Brandy GallagherSep 9, 2025
    Why is the Power LED (A) off on my Generac Power Systems Measuring Instruments?
    • C
      cgomezSep 10, 2025
      If the Power LED (A) is off on your Generac Power Systems Measuring Instruments, it indicates there is no power to the Mobile Link cellular unit. Inspect the thermal safety device (fuse, in-line circuit breaker, or thermal coupler) in the harness. Also, verify the harness is correctly connected to the battery and reset the connector to the Mobile Link cellular unit.

Summary

Safety

General Safety Guidelines

General safety guidelines and warnings for operating the equipment.

General Safety Hazards

Specific hazards related to general safety during operation and maintenance.

Electrical Safety Hazards

Hazards associated with electrical shock and electrocution during use.

Explosion and Fire Hazards

Risks of explosion and fire due to fuel, vapors, and combustible materials.

Setup and Operation

Pre-Installation Wi-Fi Signal Test

Procedure to test Wi-Fi signal strength before generator installation.

Controller Wi-Fi Setup

Detailed instructions for configuring Wi-Fi settings directly on the generator controller.

Download Mobile Link App and Register

Steps to download the app and register the generator with Mobile Link.

Troubleshooting

General Wi-Fi Troubleshooting

Common problems and solutions for Wi-Fi connection issues.

Generac Power Systems Mobile Link Specifications

General IconGeneral
CategoryMeasuring Instruments
ManufacturerGenerac Power Systems
Product NameMobile Link
FunctionRemote monitoring of generator status
CompatibilityCompatible with Generac generators
ConnectivityWi-Fi or Cellular
SubscriptionRequired
Mobile AppAvailable for iOS and Android
Monitored ParametersGenerator status
Power SourceGenerator battery