EasyManua.ls Logo

Glow-worm ENERGY 18r -A (H-GB) - Filling the Condensate Siphon; Switching on the Product; Checking the Gas Connection Pressure (Gas Flow Pressure)

Glow-worm ENERGY 18r -A (H-GB)
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-up 7
0020200958_00 SUSTAIN ..r Installation and maintenance instructions 17
Caution.
Risk of material damage if the heating
water is treated with unsuitable additives.
Unsuitable additives may cause changes in
the components, noises in heating mode and
possibly subsequent damage.
Do not use any unsuitable frost and cor-
rosion protection agents, biocides or seal-
ants.
No incompatibility with our products has been detected to
date with proper use of the following additives.
When using additives, follow the manufacturer's instruc-
tions without exception.
We accept no liability for the compatibility of any additive or
its effectiveness in the rest of the heating system.
Additives for cleaning measures (subsequent
flushing required)
Fernox F3
Sentinel X 300
Sentinel X 400
Additives intended to remain permanently in the
system
Fernox F1
Fernox F2
Sentinel X 100
Sentinel X 200
Additives for frost protection intended to remain
permanently in the system
Fernox Antifreeze Alphi 11
Sentinel X 500
If you have used the above-mentioned additives, inform
the operator about the measures that are required.
Inform the operator about the measures required for frost
protection.
7.5 Filling the condensate siphon
C
2
3
1
A
B
1. Unclip the lower section of the siphon (1) from the up-
per section of the siphon (2).
2. Remove the float (3).
3. Fill the lower section of the siphon with water up to
10 mm below the upper edge of the condensate drain
pipework.
4. Re-insert the float (3).
Note
Check whether the float is present in the
condensate siphon.
5. Clip the lower section of the siphon (1) into the upper
section of the siphon (2).
7.6 Switching on the product
Switch on the product via the main switch installed on-
site.
7.7 Checking the gas connection pressure (gas
flow pressure)
1. Close the gas isolator cock.

Table of Contents

Other manuals for Glow-worm ENERGY 18r -A (H-GB)

Related product manuals